|
|
Testing Procedures For Various Assemblies
This
section provides a description of the field test procedures for the 3
most common types of assemblies along with the number of test required
to ensure that the assembly is functioning within the standards
established by the Safe Drinking Water Act (EPA). The testing criteria
below was provided by Conbraco Mfg.
|
Type
of Assembly |
No
of Test Required |
|
Double Check valve Assembly |
2 |
|
Pressure Vacuum Breaker |
2 |
|
Reduced Pressure Zone |
3 |
Field
Test Procedures for Double Check Valve Assembly.
TEST 1:
Purpose- to check valve No#1 for tightness against reverse flow.
Steps:
- Bleed
water through all four-test cocks to eliminate foreign material.
-
Install appropriate fittings
-
Connect the high side hose to test cock #2 and connect the low side
hose to test cock#3. Connections must be drip tight.
- Open
test cocks #2 and #3, then bleed hoses, making sure to bleed the low
side last.
- Close
#2 shutoff valve; then close#1 shutoff valve.
- By
means of the highside needle valve lower the pressure at test cock #2
about 2 psi below the pressure at test cock#3. If this small
difference can be maintained then check valve #1 is reported as tight
or okay. Proceed with test #2.
- Open
shutoff valve #1 to pressurize device.
-
Loosely attach the bypass hose to test cock #1, and bleed from the
gage through the hose by opening the low side needle valve to
eliminate trapped air. Close low side needle valve. Tighten bypass
hose. Open test cock#1.
- Close
#1 shutoff valve.
- By
loosening the low side hose at test cock #3, lower the pressure in the
device about 10 psi below normal line conditions.
-
Simultaneously open both needle valves very slowly. If the check
valve is holding tight, the high-pressure gage will begin to drip
while the low-pressure gage will increase. Close needle valves. If
the gage shows that a small (no more than 5 psi) backpressure is
created and held, then the check valve is reported as “tight.”
- Close
all test cocks remove all equpment and reopen #1 shutoff valve.
-
Test
2: Purpose – to test
No #2 check valve for tightness against reverse flow. Note: a
requirement is for the check valve shall be tight against reverse flow
under all differentials.
Field Test Procedures for
Pressure Vacuum Breaker
Test
#1-
Test #2
Field Test Procedures for Reduced Pressure Zone
Test #1-
Test #2-
Test #3- |
|