|
Types of Backflow Preventers
There are 6 distinct types of mechanical assemblies
considered to be backflow prevention assemblies. They are not all
equally acceptable as protection against all types of hazards. To
determine the type of backflow prevention assembly most applicable to
the situation, the degree of hazard must be assessed along with the type
of cross- connection present. An overview of the five types of backflow
prevention assemblies as described by the Foundation for
Cross-Connection Control, and Hydraulic Research, University of Southern
California, Article “An Introduction to Cross-Connection Control is
provided as follows:
1. Air Gap
“An Air Gap is a physical separation of the supply
pipe by at least two pipe diameters (never less than one inch)
vertically above the overflow rim of the receiving vessel. In this case
line pressure is lost resulting in the need for a booster pump
downstream, unless the flow of the water by gravity is sufficient for
the after use. With an air gap there is no direct connections between
the supply main and the equipment. An air gap may be used to protect
against a contaminant or a pollutant and will protect against both back-siphonage
and backpressure. An air gap is the only acceptable means of protecting
against lethal hazards.”
2. Atmospheric (Non-Pressure) Type of Vacuum
Breaker (AVB)
“The AVB is always placed downstream from all
shutoff valves. Its air inlet valve closes when the water flows in the
normal direction. But, as water ceases to flow the air inlet valve
opens, thus interrupting the possible back-siphonage effect. If piping
or a hose is attached to this assembly and run to a point of higher
elevation, the backpressure will keep the air inlet valve closed because
of the pressure created by the elevation of water. Hence, it would not
provide the intended protection. Therefore, this type of assemble must
always be installed at least six inches above all downstream piping and
outlets.
Additionally, this assembly may not have shut-off
valves or obstructions downstream. A shut-of valve would keep the
assembly under pressure and allow the air inlet valve (or float check)
to seal against the air inlet port, thus causing the assembly to act as
an elbow, not a backflow preventer. The AVB may not b under continuous
pressure for this same reason. An AVB must not be used for more than
twelve out of any twenty-four hour period. It may be used to protect
against either a pollutant or a contaminant, but may be only be used to
protect against a back-siphonage condition.”
3. Pressure Vacuum Breaker (PVB)
“The PVB includes a check valve which is designed
to close with the aid of a spring when flow stops. It also has an air
inlet valve, which is designed to open when the internal pressure is one
psi above atmospheric pressure so that no non-potable liquid may be
siphoned back into the potable water system. Being spring-loaded it
does not rely upon gravity, as does the atmospheric vacuum breaker.
This assembly includes resilient seated shut=off valves and test-cocks.
The PVB must be installed twelve inches above all downstream piping and
outlets. The PVB may be used to protect against a pollutant or
contaminant; however, it may only be used to protect against back-ssiphonage.
It is not acceptable protection against back-pressure.”
4. Double check Valve Assembly (DCVA)
“The Double Check Valve Assembly consists of (2)
internally loaded, independently operating check valves together with
tightly closing resilient seated shut-off valves upstream of the check
valves. Additionally, there are resilient seated test-cocks for testing
of the assembly. The DC may be used to protect against a pollutant
only. However, this assembly is suitable for protection against wither
back-siphonage or back-pressure.”
5. Reduced Pressure Zone Assembly (RPZA)
“This assembly consist of (2) internally loaded
independently operating check valves and a mechanically independent,
hydraulically dependent relief valve located between the check valves.
This relief valve is designed to maintain a zone of reduced pressure
between the two check valves at all times. The RP also contains tightly
closing, resilient seated shut-off valves upstream and downstream of the
check valves along with resilient seated test-cocks. This assembly is
used for the protection of the potable water supply from either
pollutants or contaminants and may be used to protect against either
back-siphonage or back-pressure.”
6. Double Check Detector Assembly (DCDA)
“The DCDA is composed of a line-sized double check
valve assembly with a specific bypass meter and meter-sized double check
valve assembly. The meter registers accurately for very low flow rates
to detect any unauthorized use of water. This assembly is used when the
protection of a double check valve assembly is required, yet where the
added requirement of detecting any leakage or unauthorized use of water
exists. Normally their assemblies are reserved for use on fire
sprinkler lines.”
Backflow Testing Assembly Information Table.
|
Backflow Type |
Hazard Level |
Example of Use |
Testable |
|
(RPZA) Reduced Pressure Zone Assembly
|
High |
Irrigation, Toxic-poisonous connection,
multi-use building |
YES |
|
(DCVA) Double Check Valve Assembly |
Moderate/Low |
Domestic water, some irrigation |
YES
|
|
(PVB) Pressure Vacuum Breaker |
High/Highest |
Chemical, carbonation, x-ray development, etc. |
YES |
|
(DCDA) Double check Detector Assembly |
Low |
Fire protection systems, domestic water supply |
YES |
|
(AVB) Atmospheric Vacuum Breaker |
Moderate/High |
Hose bibs |
NO |
|
AirGap |
High/Highest |
Chemical, carbonation, x-ray development, etc. |
NO |
Equipment Used For Conducting Assembly Testing
The two types of equipment used for conducting
assembly testing are described as follows:
Manual- is attached to the assembly by a
technician and the testing series is conducted. The accuracy rating of
the units are within a 2/100ths rating (well within acceptable
standards). A manual unit is preferred by testers due to the cost, and
to avoid the possibility of the unit getting wet and effecting its
accuracy. Manual models are all equal in testing accuracy.
Electronic - is attached manually by a
technician and the testing series and results are preformed and
calculated by a computer. These units are within a 1/100th
to 2/100ths accuracy rating (well within acceptable standards). |